CHPgenerator120kWnaturalgenerator150kVACombineHeatPower

Natural gas generator/

120kW natural generator 6 Cylinders/ 150kVA with Combine Heat Power (CHP) system Cummins engine 6CTAA8.3-T

Basic information:

Engine: 6CTAA8.3-T
Alternator:Stamford copy/ Stamford original/Marathon/Leroy-Somer
Controller:Deepsea / China SmartGen/ ComAp
Dimension and Weight:
Silent: 3400*1500*1950(2700kg)
Open: 2500*1100*1400(1700kg)

  • Product Details
  • Inquiry

120kW natural generator 6 Cylinders/ 150kVA with Combine Heat Power (CHP) system Cummins engine 6CTAA8.3-T

Technical Parameters
 
Natural Gas Generator Technical Data
Genset HT-120 Prime Power (KW) 120
Rated frequency(Hz) 50/60 Prime Power (KVA) 150
Rated speed(Rpm) 1500/1800 Phase 3 Phase
Voltage 220/380V,230/400V, N.W (KG) 2700
240/415V,120/240V
Rated Current 216A Silent Size  (L*W*H)  mm 3450*1550*2000
 Diesel Engine Technical Data
Brand/Original Cummins Modified Type Water Cool,
Electric start
Engine Item No. 6CTAA8.3-T Cylinder No. 6
Displacement (L) 8.3 Bore and Stoke (MM) 114*135
Prime Power (KW) 138 Gas consumption 0.32m3/Kw.h
Standby power (KW) 151 Compression Ratio 11.5:1
Governor Electronic Governor Aspiration Type Turbocharged and Air Cooled
Alternator Technical Data
Brand/ Original Stamford copy/ Stamford original/Marathon/Leroy-Somer
Alternator Model HT-120D Protection IP23
Alternator Type Brushless sel-excited Insulation Class H
Phase / wire 3-phase& 4 line Factor 0.8
Control Module Specifications
Digital Control Module suitable for a wide variety of single, diesel or gas, gen-set applications. 
Monitoring an extensive number of engine parameters, the module will display 
warnings, shutdown and engine status information on the back-lit LCD screen and illuminated LEDs.
The control module gives digital readouts of:
Generator voltage Output frequency Engine hours run
Engine speed Battery voltage  
The control module has indicators for failure information:
  High water temperature         Failure to start Battery charger failure
Automatic shutdown occurs under:
Low engine oil pressure High engine water temperature
Over speed/Low speed Failure to start after three attempts

120kW natural generator 6 Cylinders/ 150kVA with Combine Heat Power (CHP) system Cummins engine 6CTAA8.3-T

Soundproof/Silent/Mobile trailer Box:

1. Silent box: Acid pickling and phosphating treatment, anti-rust, anti-corrosion 

2. Noise Level@7m: 72dB(A)                    

3. Color optional 

4. Oil tank mounted on base frame for 8-12 Hours working

5. Excellent ventilation                               

6. Security and Safety

120kW natural generator 6 Cylinders/ 150kVA with Combine Heat Power (CHP) system Cummins engine 6CTAA8.3-T

Jiangsu Haut Mechanical Co., Ltd,  is located in Yangzhou City.Jiangsu Province . Adjacent to Shanghai Port. With convenient transports access.For more than 20 years.The power of generating units range from 10 kw to 5000 kw.They all adopt automation silence. mobile. and remote monitoring.Our can provide all kinds of diesel generators according to your requirements. Our products are widely used in factories. communication engineering. military. ports. roads.railways and commercial facilities.

Basic data of combined heat and power

1.LPG gas inlet pressure:: Low Intake Pressure of LPG Gas 3.5-7.0kPa

2.Max. ambient temp.:+38C, Min.temp.:-28C

3.Electricity-led operation

4.Island use (not selling electricity to the Grid)

5.Pressure of LPG gas supply: 0.005MPa (5KPa)

6.Continuous COP running with 24/7/350 (approx. 15 days for normal maintenance)

Remarks

1.The technical data are based on LPG gas with a calorific value of 36 MJ/Nm³ and a methane no. >80

2.The technical data indicated is based on standard conditions acc to DIN ISO 3046-1 Standard conditions:                                   

-Atmospheric pressure absolute: 100 kPa

-Air temperature 25 °C

-Relative air humidity 30 %

3.The technical rating adaptation at ambient conditions acc to DIN ISO 3046-1

-The tolerance for the specific fuel consumption is + 5 % at rated output

-The tolerance for the usable heat is 7 % at rated output

-The coolant data are based on a 40 % portion of antifreeze

Heat Recovery System

1.The power produced during the CHP operation can meet the

demand of users, at the same time, a mass of heat in the jacket

water and exhaust gas can be recovered through heat exchangers,

heat recovery boilers to provide heat.

2.Plate Heat Exchanger for Jacket Water Heat and for Oil Cooling

3.Shell & Tube Heat Exchanger for Exhaust Gas

4.Special anti-corrosion treatment  

 

Waste heat recovery parameters

Thermal power: 165.6kW

Hot water output: 6.79T/h

Thermal efficiency: 50%

Comprehensive efficiency: 87.4%

Hot water output: 90℃

Our Advantages:

1. Solve technical problems and provide international warranty service for the engine within 24 hours

2. Design customized products according to customer requirements

3. Polyester varnish, anti-corrosion, protect the appearance and prevent rain

4. Test for two hours before delivery

5. ISO9001 and CE certification, strictly guarantee the quality

120kW natural generator 6 Cylinders/ 150kVA with Combine Heat Power (CHP) system Cummins engine 6CTAA8.3-T

Standard configuration:

1. Generator Set Distributor Random Technical Documents   

2. Diesel engine, radiator / Muffler / Unit manual

3.  Alternator  / connection elbow  / unit product quality certificate

4.  Steel structure chassis  / Battery and cable  / Control screen

5.  MCCB air protection switch  / Damping pad  / Engine original quality file

6.  Generator original quality documentsce